MODBUS to PROFIBUS gateway technical indicators:
(1) The gateway has two functions on the MODBUS side: the gateway of the MM function is a slave station on the PROFIBUS-DP side, and the MODBUS master station on the MODBUS side; the gateway of the MS function is a slave station on the PROFIBUS-DP side, The MODBUS side is a MODBUS slave station; the interface realizes data transparent communication between PROFIBUS and MODBUS through data mapping of the PROFIBUS communication data area and the MODBUS data area;
(2) MODBUS 01H, 02H, 03H, 04H, 05H, 06H, 0FH, 10H functions are supported regardless of whether the MODBUS master station or the slave station is used;
(3) PROFIBUS-DP protocol, in accordance with; JB/T 10308.3-2001: Measurement and control of digital data communication - Fieldbus for industrial control systems - Part 3: PROFIBUS specification;
(4) Standard PROFIBUS-DP drive interface, baud rate adaptive, maximum baud rate 12M;
(5) The number of inputs/outputs on the PROFIBUS side can be freely set by the user in the following three ranges:
1Input Bytes + Output Bytes ≤ 232 Bytes;
2 Max Input Bytes ≤ 224 Bytes;
3 Max Output Bytes ≤ 224 Bytes.
(6) Standard RS-232/485 interface, half-duplex, baud rate is optional at 2400, 4800, 9600, 19.2K, 38.4K, 57.6K; check digits (even, odd, none) are optional;
(7) RS232/485 maximum communication message length: send 230 bytes, accept 230 bytes;
(8) Wide voltage power supply: 10~30VDC, 200mA;
(9) Working environment temperature: -20-65 ° C;
(10) Storage temperature: -40 to 80 ° C;
(11) Relative humidity: ≤90% (no condensation);
(12) Installation: 35mm rail;
(13) Protection level: IP20.
(14) Product size: 40x110x74 (mm)